Electrical Safety Device: Air Circuit Breaker (ACB)

Generators onboard ships are the power suppliers for the entire vessel as they stand as the primary source of power to all running machineries including the propulsion plant. For this reason, safe and efficient running of the ship generator has to be given highest consideration. One of the important safety devices used for ship’s generator is Air Circuit Breaker (ACB).

Air circuit breaker is designed to overcome the defects and safeguard the machine before it breakdowns.

The main function of air circuit breaker is to:

–          Open and close a 3 phase circuit, manually or automatically.

–          Open the circuit automatically when a fault occurs. Faults can be of various types – under or over voltage, under or over frequency, short circuit, reverse power, earth fault etc.

–          The main feature of ACB is that it dampens or quenches the arcing during overloading.

Air Circuit Breaker (ACB) Construction & Working

Air Circuit Breaker

ACB has two sets of contacts i.e. main and auxiliary contacts. Each set of contact consists of a fixed contact and a moving contact. The main contact normally carries most of the load current. All the contacts are made of cadmium-silver alloy which has very good resistance to damage by arcing.

When the ACB is closed, the powerful spring is energized and the ACB is than latched shut against spring pressure. The auxiliary contact makes first & breaks last i.e. when ACB is closed, the auxiliary contact closes first then the main contact follows.

When the ACB is open, the main contact open firsts and then auxiliary contact opens. Thus the auxiliary contacts are subjected to arcing during the opening of ACB and can easily be replaced.

The main contact closing pressure is kept high so that the temperature rise in the contacts while carrying current remains within limit. Closing coil operating on D.C voltage from a rectifier is provided to close the circuit breaker by operating a push button.

How Arc Quenching is Achieved?

Quenching of arc is achieved by:

1.Using arcing contacts made of resistance alloy and silver tips for the main contacts. Arcing contacts close earlier and opens later than the main contacts.

2.When opening contacts have long travelled at high speed to stretch the resultant arc, which is transferred to the arcing contact.

3.Cooling and splitting of the arc is done by arc chutes which draw the arc through splitters by magnetic action and quickly cool and split the arc until it snaps. The circuit breaker opens when the arc is quenched.

Reference: Book on Marine Electrical equipment by H.D.McGeorge

Do you have info to share with us ? Suggest a correction

Article Footer Banner
Article Footer Banner

Subscribe To Our Newsletters

By subscribing, you agree to our Privacy Policy and may receive occasional deal communications; you can unsubscribe anytime.

Web Stories

About Author

An ardent sailor and a techie, Anish Wankhede has voyaged on a number of ships as a marine engineer officer. He loves multitasking, networking, and troubleshooting. He is the one behind the unique creativity and aesthetics at Marine Insight.

6 Comments

  1. what will be the curent capacity of the flexible contacts of 2000 A air circuit breaker

  2. Can you please explain how bus bar is interconnected and construction and working of the interconnector and how reverse power trip is SIMULATED???

Leave a Reply

Your email address will not be published. Required fields are marked *